After considering the queries, clarifications, recommendations and suggestions, the BAC4IGOV hereby decides to include, revise, amend, delete and/or adapt the following provisions:

Query BAC4IGOV’s Response
For all server requirements, can we remove the TECHNICAL SPECIFICATIONS portion and just use the HARDWARE SUMMARY portion as reference for all server configurations?

The specifications pertains to one brand.

 

Example: System BIOS and Power Supply

The technical specifications section details each hardware component that comprises the server system. The power supply specification is required based on our data center rack layout design. Specifications indicated in the TOR are minimum requirements and should not be treated as absolute.

 

For all server requirements, instead of all Accessories listed under HARDWARE SUMMARY can we use manufacturer’s standard or include the phrase “or equivalent”? The specifications pertains to one brand. Kindly refer to the Supplemental Bid Bulletin #1 issued. Some of the items under the Accessories are removed. Items that were not removed are minimum requirements and are not brand-specific. Example:

1.1.1.        Accessories:

                                          1.1.1.1.        One (1) 8 pin to 8 pin ribbon SGPIO cable with tube , 40cm, PBF

                                          1.1.1.2.        One (1) set of 4 SATA 56/45.5/35/23CM round S-RA. 26AWG

                                          1.1.1.3.        Riser Card Support

                                          1.1.1.4.        Two (2) 1U Passive Custom CPU Heat Sink

1.1.1.5.        Two (2) 1U  400W Redundant Short Depth Power Supply

1.1.1.6.        One (1) Quick-release, tool-less mounting rail kit

1.1.1.7.        Two (2) C14 to C13 power cord, 1 meter

1.1.1.8.        Two (2) units of 10Gb, pluggable copper cable assembly with integrated SFP+ transceivers, 3 meters

1.1.1.9.        Two (2) units of 10Gb, pluggable copper cable assembly with integrated SFP+ transceivers, 1 meter

For all server requirements, in complying with the total memory and storage of the servers can we use a different configuration however maintaining the same capacity for the DIMM (memory) and HDD (hard disk) required?

Example: 32GB memory can be fulfilled either by 4 x 8GB or 2 x 16GB.

No. We have designed the configuration to accommodate future upgrades.

 

For Openstack Compute Nodes (p.99) and Compute Nodes (p. 157), can we propose 2 units of 1U serves instead of 2U 2 nodes? We can give you the same performance and better redundancy with the same space requirement. Again, 2U 2 nodes pertains to a certain brand. No. Two (2) units of 1U servers would need four (4) electrical outlets from the PDU. Whereas the 2U 2 node configuration would require only two (2). The 2U 2 nodes are not brand-specific.

 

For Openstack Compute Nodes, processor specified (E5-2697v2) is only scalable up to 2 processors per node but quantity stated is 4. Can we interpret all hardware specifications is total for 2 nodes combined? Yes.
For 4U Ceph Nodes, the amount of disks needed within a 4U rack space is pointing to one brand. Suggestion is to focus on total capacity (for SSD and SAS/SATA) while maintaining the initially allocated 4U rack space. The 4U Ceph Nodes specifications are not brand-specific.

 

To ensure compatibility and support with most Hardware vendors, suggestion is to use Enterprise Linux, either RHEL or SUSE, Yes.
10/40Gpbs Layer 3 Ethernet Switches (Page 114, 7.11.1 IT Equipment Safety Standards) – 7.11.1.5  EN 60825-1+A2:2007 = May we request to change the requirement to EN 60825-1:2—7 and omit the “+A2”? This might be a typographical error for this standard do not have “+A2”. Yes. You may omit the +A2.

 

10/40Gpbs Layer 3 Ethernet Switches (Page 115, 7.11.12. EMI/EMC Standards) – 7.11.2.13. EC/EN 61000-4-3:2006+A2:2010, Radiated Immunity, 80-25000MHz= May we request to change 80-25000MHz to 80-25000Mhz? This might be a typographical error for this should only be 2500Mhz which is the standard frequency. Yes. This is a typographical error. It should be 80-2500MHz.
10/40 Gpbs Layer Ether Switches (Page 115, 7.11.4. IEEE 802.3 Media Access Standards)- 7.11.4.1. to 4 (IEEE 802.3ab 1000BASE-T, IEE 802.3z 1000BASE-X, IEEE 802.3ae 10GBASE-X, and IEE 802.3ba 40GBASE-X) means that the 10/40Gpbs Layer 3 switches should be able support this type standards? For this will depend on the SFP Transceivers you are going to use on the switch. Yes.
10/40Gpbs Layer 3 Ethernet Switches (Page 110) – We would like to clarify what kind of Training and Certification do you require for this item? Can this be done during the installation in your office and transfer of knowledge of the product? Yes.
Core Switch Module- We would like to clarify if you already have the Core switch box and that you only need additional switch modules on your existing core switch? Or should we provide Core Switch with 2×48 ports switch modules installed in the core switch? Yes, we have an existing core switch and we only need additional core switch modules for this lot.

 

 

SAN Storage of management Rack – 1. Can we change the onboard dual-port Lan of the SAN storage to 1Gbe? For the reason that the 10Gbe LAN is optional and can only be added through the available expansion slot of the SAN storage and it is not onboard/built-in in the SAN storage. 2. We would like to clarify about the SAN storage if the “supports up to 500k IOPS” is only the capability of the SAN storage if configured in full clustered by adding storage expansion? 1.    Yes.

2.    We have changed this part to: “Supports around 90k IOPS”

 

May we know, what is your existing Rack Cabinet brand in order to provide compatble 1u tool less rack filler including mounting holes and clips? APC Rack cabinets
I. Supply, Delivery, Installaton and Configuration of One (1) Lot of OpenStack Cloud System

a) Admin Node

1.1.2. Barebone: 1U – 4x SATA/SAS2 – Integrated LSI 2208 6G SAS Raid Controller with BBU – 8x DDR3 – 400W Redundant. Can you please relax it to 400W-460W Redundant?

No. The power supply is based on our data center rack layout design.

 

 

 

1.1.6. Nework Card: One (1) 4-port SFP+10GbE network card. Please allow us to propose 2 networking card with 2 ports each. Yes.
1.1.7.5. Two (2) 1U 400W Redundant Short Depth Power Supply. Can you please relax it to Two (2) 1U 400W – 460W Redundant Short Depth Power Supply? No. The power supply is based on our data center rack layout design.
1.2.6.6. Two (2) Fast UART 16550 serial ports. Please allow us to propose 1 Fast UART serial ports. Yes.
b) Ceph Monitor Node

> 2.1.2. Barebone: 1U – 4x SATA/SAS2 – Integrated LSI 2208 6G SAS RAID Controller with BBU – 8x DDR3 – 400Q Redundant. Can you please relax it to 400! – 460W Redundant?

No. The power supply is based on our data center rack layout design.

 

2.1.6. Network Card: One (1) 4 –port SFP+ 10GbE network card. Please allow us to propose 2 networking card with 2 ports each. Yes.
2.1.7.5. Two (2) 1U 400W Redundant Short Depth Power Supply. Can you pleae relax it to Two (2) 1U 400W – 460W Redundant Short Depth Power Supply? No. The power supply is based on our data center rack layout design.
2.2.6.4.1. Four (4) Rear USB 2.0 ports. Please allow us to propose 2 front, 2 rear and 1 onboard USB 2.0 ports? Yes.
2.2..6. Two (2) Fast UART 16550 serial ports. Please allow us to propose 1 Fast UART serial ports? Yes.
c) OpenStack Controller Nodes

> 3.1.2. Barebone: 1U – 4x SATA/SAS2 – Integrated LSI 2208 6g SAS RAID Controller with BBU – 8x DDR3 – 400W Redundant. Can you please relax it to 400W – 460W Redundant?

No. The power supply is based on our data center rack layout design.
3.2.6.4.1. Four (4) Rear USB 2.0 ports. Please allow us to propose 2 front, 2 rear and 1 onboard USB 2.0 ports? Yes.
3.2.6.6. Two (2) FastUART 16550 serial ports. Please allow us to propose 1 Fast UART serial ports? Yes.
d) OpenStack Compute Nodes

>4.1.6. Network Card: Two (2) 4-port SFP+ 10GbE Network Card. Please allow us to propose Four (4) 2-port 10GE networking each?

Yes.
>4.1.7.4 Two (2) 1280W 1U Redundant PSU with queit mode. Please allow s to propose Two (2) 750 W Redundant PSU with quiet mode. Yes.
>4.2.6.6. One (1) Fast UART 16550 port/1 Header. We would like to request for this item to be removed from the TOR since this is not usually used. Yes.
>4.2.7.2. Two (2) PCI-E 3.0 (x8) full-height full-length slots. Please allow us to propose One half-height half-length PCIe 3.0 x 8 slots and Two half-height half –length PCIe 2.0×8 slots instead. Yes. We have removed this part. Please see Supplemental Bid Bulletin #1 for this.
> 4.2.13.1. 1280W redundant high-efficiency digital power supply with PMBus 1.2. Please allow us to propose 750W Redundant PSU. Yes. You may propose 750W redundant PSU. Please note that the digital power supply with PMBus 1.2 is a minimum requirement.
>4.2.213.1. 1000W @ 100-140V, 50-60Hz, 8-12A. Please allow us to propose 750W Redundant PSU. Yes. You may propose 750W redundant PSU provided that the power rating for 180-240V is included.
>4.2.13.2.2. 1280W @180-240V, 60-50Hz, 6-8A. Please allow us to propose 750W Redundant PSU. Yes. You may propose 750W redundant PSU provided that the power rating for 180-240V is included.
2) Ceph OSD Nodes

>5.1.2. Barebone: 2U – 24 x SATA/SAS – LSI 2308 6G SAS -16 xDDr3 – 920W Redundant. Please allow us to propose 750W Redundant PSU.

Yes.
>5.1.9.5 Two (2) 920W 1U Redundant PSU with quiet mode. Please allow us to propose two (2) 750W Redundant PSU with queit mode. Yes.
>5.2.7.5.1. Four (4) Rear USB 2.0 ports. Please allow us to propose two (2) Rear USB ports and two (2) Front USB ports. Yes.
>5.2.15.1. 920W redundant high-efficiency (94%+) AC-DC power supplies with PMBus and I2C. Please allow us to propose two (2) 750W Redundant PSU with quiet mode. Yes. You may propose 750W redundant PSU. Please note minimum requirement of AC-DC power supplies with PMBus and I2C.
II. Supply, Delivery, Installation and Configuraiotn of One (1) Lot of Object-based Storage System

a) Ceph Monitor Nodes

>1.17. Network Card: One (1) 4-port SFP+ 10GbE network card. Please allow us to propose 2 networking card with 2 parts each.

Yes.
b) 4U Ceph OSD Node

>2.1.2. Barebone: 4U – 36 SATA/SAS – LSI 2308 6G SAS 1 DDR3 – 1280W Redundant. Please allow us to propose 1200W PSU instead.

Yes
>2.1.8. Network Card: One (1) 4-port SFP+ 10GbE network card. Please allow us to propoase 2 networing cad with 2 ports each. Yes
>2.2.7.5.1. Four (4) rear USB 2. Ports. Please allow s to propose 2 Rear USB ports and 2 Front USB ports. Yes.
>2.2.7.5.2. Four (4) via header USB 2.0 ports. Please allow us to propose USB ports and 2 Fron USB ports. Yes
>2.2.15.1. 1280W high-efficiency (95%+) power supply. Please allow us to propose 1200WPSU instead. Yes. You may propose 1200W PSU. Please note minimum requirement is a high-efficiency (95%+) power supply.
III. Supply, Delivery, Installation and Configuration of One (1) Lot of Data Warehouse System

a) Storage Nodes

>1.1.2. Barebone: 2U – 24 x SATA/SAS – LSI 2308 6G SAS – 16 x DDR3 – 920W Redundant. Please allow us to propose 750W Redundant PSU.

Yes.
>1.1.8. Network Card: One (1) 4-port SFP+ 10GbE network card. Please allow us to propose 2 netowrking card with 2 ports each. Yes.
>1.1.19.5. Two (2) 920W 1U Redundant PSU with quiet mode. Please allow us to propose 750W Redndant PSU instead. Yes. You may propose 750W redundant PSU. Please note the PSU with quiet mode as a minimum requirement.
>1.2.7.5.1. Four (4) Rear USB 2.0 ports. Please allow us to propose 2 Rear USB ports and 2 Front USB ports. Yes
>1.2.8.5.1. Four (4) via header USB 2.0 ports. Please allow us to propose 2 Rear USB ports and 2 Fron USB ports. Yes
>1.2.8.1. Five (5) PCI-E 3.0 (x8) low-profile slots. Please allow us to propose one for a full height full-length PCIe card, one for a full height 3/4-length PCIe Card, one for full height full-length PCIe card, three for half-height standard PCIe cards, and one dedicated for a RAID controller card. Yes. We have removed this part. Please see Supplemental Bid Bulletin #1.

 

>1.2.15.1. 920W redundant (94%+ efficiency) AC-DC with PMBus and I2C. Please allow us to propose PSU. Yes. You may propose 750W redundant PSU. Please note the 94%+ efficiency AC-DC with PMBus and I2C as its minimum requirement.
IV. Supply, Delivery, Installation and Configuration of One (1) Lot of Management Cluster System

a) Monitor Server

>1.2.8.5. Four (4) via Header USB 2.0 ports. Please allow us to propose 2 front, 2 rear and 1 onboard USB 2.0 ports.

Yes
b) Compute Servers

>2.1.2. Barebone: 2U – 2 nodes – 24 x SATA/SAS – LSI 2008 6G SAS -1280 or 1620W Redundant. Please alow us to propose 4U-2Node-2 HDD Slot or 2U-2Node- 16 HDD Slot with 750W redundant.

No.
>2.1.7.3. Two (2) 1280W 1U redundant single output PSU. Please allow us to propose 750W redundant PSU. Yes. You may propose 750W redundant PSU. Please note the single output PSU as minimum requirement.
>2.2.7.2. Two (2) PCI-E 3.0 (x8) full-height full-length slots. Please allow us to propose one half-height half-length PCIe 3.0 x8 slot and Two half-height half-length PCIe 2.0 x8 slots. Yes. We have removed this part. Please see Supplemental Bid Bulletin #1.
>2.2.13.1. 1280 or 1620 redndant high-efficiency digital PSU with PMBus 1.2. Please allow us to propose 750W redundant. Yes. You may propose 750W redundant. Please note high-efficiency digital PSU with PMBus 1.2 as minimum requirement.
>2.2.13.2.1. 1000W @100-140V, 50-60Hz, 8-12A. Please allow us to propose 750W redundant. Yes. You may propose 750W redundant provided that the power rating for 100-140V is included.
>2.2.13.2.2. 1280W @ 180-240V, 50-60Hzm 6-8A. Please allow us to propose 750W redundant. Yes. You may propose 750W redundant provided that the power rating for 180-240V is included.
>2.2.13.3.1. 1000W: +12V/83A; +5Vsb/4A. Please allow us to propose 750W redundant. Yes. You may propose 750W redundant provided that the power ratings for +12V/83A and +5Vsb/4A are included.
>2.2.13.3.2. 1280W: +12V/106.7A, +5Vsb/4A. Please allow us to propose 750W redundant. Yes. You may propose 750W redundant provided that the power ratings for +12V/106.7A and +5Vsb/4A are included.
Item 5  p.  185  of  Software portion of the  bid  refers  to a Server Management Software.   It  appears  that this is the specific management software  of a server  brand.  As such  it should be part  of the hardware portion  of the bidding  and not on the software part.  Software  bidder cannot supply this as they cannot know the specific brand of server, hence server management software,  as it is also being bid for simultaneously. We moved this to the Hardware Lot.
Please validate consistency of the required quantity of OpenStack Controller Nodes, and hence the required subscription for OpenStack controller nodes.  It  appears the needed value is six(6)  [ on pages 85, 219,221 ) of the bid documents  but  it states  three (3) are needed on page 94 of the bid documents As a minimum requirement, the quantity of the OpenStack Controller Nodes should be six (6) units. The quantity indicated under the HARDWARE SUMMARY of this item is a typographical error.
Please validate consistency of the required quantity of  Ceph Monitor  Nodes,  and hence the required subscription for Ceph Monitor nodes.  It  appears the needed value is three(3)  [ on pages 85, 90 ] of the bid documents  but  it states  six (6) are needed on page 219 and 221 of the bid documents As a minimum requirement, the quantity of the Ceph Monitor Nodes of the OpenStack Rack should be three (3) units. The quantity indicated at pages 219 and 221 of the bid documents is a typographical error.
Input/Output: Four (4) rear USB 2.0 pots and Two (2) via header USB 2. Ports under Content No.1 (1.2.6.4 and 5.2.7.5), Content No.2 (2.2.7.5), Content No. 3 (1.2.7.5) and Content No. 4(1.2.8.4 and 1.2.8.5).

–      May we request to consider just the total number of USB Ports irregardless of its location/ position in the server.

Specifications for the USB 2.0 ports “rear” positioning and the “via header USB 2.0 ports” are removed.

 

Operating Environment/Compliance: Environmental Specifications under Content No. 1 (1.2.13; 2.2.13; 3.2.12.2; 4.2.12.2 and 5.2.14.2.4), Content  No. 2 (1.2.13.2 and 2.2.14), Content No. 3 (1.2.14.2) and Content No. 4 (1.2.14.2 and 2.2.12.2).

–      Aside from the ROHS compliance, on the detailed Environmental Specifications, may we request to read as follow “Environmental Specifications or equivalent based on ASHRAE Class A3 thermal guidelines”.

No. The ASHRAE Class A3 covers data center environment guidelines while the RoHS directive covers substance restrictions.

 

Power Supply: AC Input, DC Output and Power Distributor under Content No. 1 (1.2.10; 2.2.10; 3.2.10; 4.2.10 and 5.2.12), Content No. 2 (1.2.11 and 2.2.12), Content No. 3 (1.2.12) and Content No. 4 (1.2.12 and 2.2.10)

–      May we request to remove the detailed technical specifications and consider manufacturer’s standard and certification compliance.

Power specifications are modified: “AC Input” and other power input specifications are retained while the “DC Output” and “Power Distributor” requirements are removed.

 

Below are the amended provisions:

Original Provision Amended Provision
Section III. Bid Data Sheet (BDS)

1.2 The lot and reference is: BAC4IGOV-2015-107-048

Section III. Bid Data Sheet (BDS)

1.2 The lot and reference is: BAC4IGOV-2015-10-048

 

Original Provision Amended Provision
Section VII. Technical Specifications
LOT 1: Supply, Delivery, Installation and Configuration of the One (1) Lot of Government Common Platform Hardware
No Stipulation CONTENTS:

7. Supply, Delivery, Installation and Configuration of Server Management Software

No Stipulation Supply, Delivery, Installation and Configuration of One (1) Lot of Server Management Software

 

   1.        Server Management Software

1.1.        TECHNICAL SPECIFICATIONS (Minimum Requirements)

1.2.        Subscription

1.2.1.        Quantity of licenses must be sufficient for the Management Cluster System mentioned in the One (1) Lot of Government Common Platform Hardware’s Terms of Reference

1.2.2.        One (1) year subscription/licenses with 24 x 7 support

1.3.        Features

1.3.1.        Must have support for remote management of server health, power consumption and firmware maintenance using agent and agent-less mechanisms

1.3.2.        Must have support for optimizing the power consumption of server rack

1.3.3.        Must have support for monitoring and applying policies to maximize compute density per rack and avoid unexpected server shutdowns

1.3.4.        Must enable management of system BIOS upgrades and configuration uniformly across multi-environment deployments through baseboard management controller (BMC/IPMI)

1.3.5.        Must support performing of parallel firmware upgrades, system memory and power commands, and more through Secure Socket Layer (SSL)

1.3.6.        Must be able to perform monitoring, configuration and update operations without affecting application performance or continuity using out-of-band (OOB) utilities

1.3.7.        Must have server management functions which include command line interfaces to support existing data center automated management frameworks.

1.4.        Hardware Requirements

1.4.1.        At least x86 server

1.4.2.        At least 200MB free disk space

1.4.3.        At least 64MB available RAM

1.4.4.        Ethernet network interface card

1.5.        OS Requirements

1.5.1.        Linux:

                                        1.5.1.1.        Red Hat Enterprise Linux Server 5.x (64-bit),

                                        1.5.1.2.        Red Hat Enterprise Linux Server 6.x (64-bit),

                                        1.5.1.3.        SUSE Linux Enterprise 11.x (64-bit)

1.5.2.        Windows:

                                        1.5.2.1.        Windows 2003 Server R2 (64-bit),

                                        1.5.2.2.        Windows 2008 Server R2 (64-bit)

1.6.        Browser Requirements

1.6.1.        OPEN JDK / Oracle JRE 1.6.0 or later

1.7.        Firmware Requirements

1.7.1.        Internet Explorer 8.x or higher,

1.7.2.        Firefox 3.x or higher

1.7.3.        Screen Resolution: 1024 x 768

1.8.        Training and Certification

1.8.1.        The proposed cloud solution must have provision for training and certification of a minimum of two (2) personnel identified by the Project.

Supply, Delivery, Installation and Configuration of One (1) Lot of OpenStack Cloud System
1.1.2 400W Redundant 1.1.2. 400W maximum redundant
1.1.7.1 Two (1) 1U 400W Redundant Short Depth Power Supply 1.1.7.1 Two (1) 1U 400W maximum Redundant Short Depth Power Supply
1.2.6.4.1. Four (4) Rear USB 2.0 ports 1.2.6.4.1. Four (4)  USB 2.0 ports
1.2.6.4.2. Two (2) via header USB 2.0 port This item is deleted.
1.2.6.6. Two (2) Fast UART 16550 serial ports 1.2.6.6. Two (2) Fast UART serial ports
1.2.10.1. 400W redundant 1.2.10.1. 400W maximum redundant
1.2.10.3.   DC Output

1.2.10.3.1.   3A @ +5V standby

These items are deleted.
1.2.10.4.  Power Distributor

1.2.10.4.1.   25A @ +5V

1.2.10.4.2.   25A @ +3.3V

1.2.10.4.3.   0.6A @ -12V

These items are deleted.
2.1.2. 400W Redundant 2.1.2. 400W maximum Redundant
2.1.7.1. Two (2) 1U  400W Redundant Short Depth Power Supply 2.1.7.1. Two (2) 1U  400W maximum Redundant Short Depth Power Supply
2.2.6.4.1. Four (4) Rear USB 2.0 ports 2.2.6.4.1. Four (4) USB 2.0 ports
2.2.6.4.2.  Two (2) via header USB 2.0 ports This item is deleted.
2.2.6.6. Two (2) Fast UART 16550 serial ports 2.2.6.6. Two (2) Fast UART serial ports
2.2.10.1. 400W redundant 2.2.10.1. 400W maximum redundant
DC Output and Power Distributor specifications of the Ceph Monitor Node:

2.2.10.3.   DC Output

2.2.10.3.1.   3A @ +5V standby

2.2.10.4.  Power Distributor

2.2.10.4.1.   25A @ +5V

2.2.10.4.2.   25A @ +3.3V

2.2.10.4.3.   0.6A @ -12V

These items are deleted.
2.1.2. 400W Redundant 2.1.2. 400W maximum Redundant
2.1.7.1 Two (2) 1U  400W Redundant Short Depth Power Supply 2.1.7.1 Two (2) 1U  400W maximum Redundant Short Depth Power Supply
2.2.6.4.1. Four (4) Rear USB 2.0 ports 2.2.6.4.1. Four (4) USB 2.0 ports
2.2.6.4.2.  Two (2) via header USB 2.0 ports This item is deleted.
2.2.6.6. Two (2) Fast UART 16550 serial ports 2.2.6.6. Two (2) Fast UART serial ports
2.2.10.1. 400W redundant 2.2.10.1. 400W maximum redundant
2.2.10.3.   DC Output

2.2.10.3.1.   3A @ +5V standby

2.2.10.4.  Power Distributor”

2.2.10.4.1.   25A @ +5V

2.2.10.4.2.   25A @ +3.3V”

2.2.10.4.3.   0.6A @ -12V

These items are deleted.
3.1.2. redundant 400W 3.1.2. redundant 400W maximum
3.1.7.1.        Two (2) 1U  400W Redundant Short Depth Power Supply 3.1.7.1. Two (2) 1U  400W maximum Redundant Short Depth Power Supply
3.2.6.4.1. Four (4) Rear USB 2.0 ports 3.2.6.4.1. Four (4) USB 2.0 ports
3.2.6.4.2.Two (2) via header USB 2.0 ports This item is deleted.
3.2.6.6. Two (2) Fast UART 16550 serial ports 3.2.6.6. Two (2) Fast UART serial ports
3.2.10.1. 400W redundant 3.2.10.1400W maximum redundant
OpenStack Controller Nodes :

3.2.10.3.   DC Output

3.2.10.3.1.   3A @ +5V standby

3.2.10.4.  Power Distributor

3.2.10.4.1.   25A @ +5V

3.2.10.4.2.   25A @ +3.3V

3.2.10.4.3.   0.6A @ -12V

These items are deleted.
4.1.2. 1620W Redundant 4.1.2. 1280W or 1620W maximum Redundant
4.1.7.1. Two (2) 1280W 1U Redundant PSU with quiet mode 4.1.7.1. Two (2) 1280W maximum 1U Redundant PSU with quiet mode
4.2.6.4.1. Two (2) Rear USB 2.0 ports 4.2.6.4.1. Two (2) USB 2.0 ports
4.2.6.6. One (1) Fast UART 16550 port /1 Header 4.2.6.6. One (1) Fast UART port
4.2.10.1. 1280W redundant 4.2.10.1. 1280W maximum redundant
4.2.10.2.1. 1000W @ 100-140V, 50-60Hz, 8-12A 4.2.10.2.1. 1000W @ 100-140V, 50-60Hz, 8-12A or equivalent rating if less than 1000W
4.2.10.2.2. 1280W @ 180-240V, 60-50Hz, 6-8A 4.2.10.2.2. 1280W @ 180-240V, 60-50Hz, 6-8A or equivalent rating if less than 1280W
DC Output specifications of the OpenStack Compute Nodes:

4.2.10.3.   DC Output

4.2.10.3.1.   1000W: +12V/83A; +5Vsb/4A

4.2.10.3.2. 1280W: +12V/106.7A, +5Vsb/4A

 

These items are deleted.
5.1.2. 920W Redundant 5.1.2. 920W maximum Redundant
5.1.9.1. Two (2) 920W 1U Redundant PSU with quiet mode 5.1.9.1. Two (2) 920W maximum 1U Redundant PSU with quiet mode
5.2.7.5.1. Four (4) Rear USB 2.0 ports 5.2.7.5.1. Four (4) USB 2.0 ports
5.2.7.5.2. Four (4) via header USB 2.0 ports This item is deleted.
5.2.7.7. One (1) Fast UART 16550 port /1 Header 5.2.7.7. One (1) Fast UART port
5.2.11.1. 920W redundant 5.2.11.1. 920W maximum redundant
DC Output specifications of the Ceph OSD Nodes:

5.2.11.3.   DC Output

5.2.11.3.1.   4A @ +5V standby

5.2.11.3.2.   75A @ +12V

 

These items are deleted.
6.6.3. 19.8W 6.6.3. 19.8W max
7.12.1.1. 550W AC power supplies 7.12.1.1. 550W maximum AC power supplies
“lowline full load” and “Output Power” specifications under the “10/40Gbps Layer 3 Ethernet Switches:

7.12.1.2.2.2.   7.5A input @ 90V (lowline full load)

7.12.1.2.5.   Output Power

7.12.1.2.5.1.   12V output, 45A max, 540W

7.12.1.2.5.2.   3.3V output, 3A max, 9.9W

7.12.1.2.5.3.   550W DC output maximum continuous

These items are deleted.
Supply, Delivery, Installation and Configuration of One (1) Lot of Object-Based Storage System
1.1.2. 700/750W Redundant 1.1.2. 700/750W maximum Redundant
1.2.7.4.1. Two (2) rear USB 2.0 ports 1.2.7.4.1. Two (2) USB 2.0 ports
1.2.7.4.2.  Two (2) via header USB 2.0 ports This item is deleted.
1.2.7.6.1. One (1) Fast UART 16550 port /1 Header 1.2.7.6.1. One (1) Fast UART port
1.2.11.1. 700W/750W redundant 1.2.11.1. 700/750W maximum redundant
1.2.11.2.1. 700W @ 100-140V, 50-60Hz, 8.5-6A 1.2.11.2.1. 700W @ 100-140V, 50-60Hz, 8.5-6A or equivalent rating if less than 700W
1.2.11.2.2. 750W @ 180-240V, 60-50Hz, 5-3.8A 1.2.11.2.2. 750W @ 180-240V, 60-50Hz, 5-3.8A or equivalent rating if less than 750W
“DC Output”  and “Power Distributor” specifications of the “Ceph Monitor Nodes” :

1.2.11.3.   DC Output

1.2.11.3.1.   +5V standby, 3A

1.2.11.3.2.   +12V, 700W: 58A @ 100-140V

1.2.11.3.3.   +12V, 750W: 62A @180-240V

1.2.11.4.   Power Distributor

1.2.11.4.1.   +5V, 25A

1.2.11.4.2.   +3.3V, 25A

1.2.11.4.3.   -12V: 0.6A

These items are deleted.
2.1.2. 1280W Redundant 2.1.2. 1280W maximum Redundant
2.1.9.2. Two (2) 1280W 1U Redundant PSU 2.1.9.2. Two (2) 1280W maximum 1U Redundant PSU
2.2.7.5.1. Four (4) rear USB 2.0 ports 2.2.7.5.1. Four (4) USB 2.0 ports
2.2.7.5.2. Two (2) via header USB 2.0 ports This item is deleted.
2.2.7.7.1. One (1) Fast UART 16550 port /1 Header 2.2.7.7.1. One (1) Fast UART port
2.2.12.1. 1280W 2.2.12.1. 1280W maximum
2.2.12.2.1. 1000W output: 100-140V, 50-60Hz, 12-8A 2.2.12.2.1. 1000W: 100-140V, 50-60Hz, 12-8A or equivalent rating if less than 1000W
2.2.12.2.2. 1280W output: 180-240V, 50-60Hz, 8-6A 2.2.12.2.2. 1280W: 180-240V, 50-60Hz, 8-6A or equivalent rating if less than 1280W
DC Output specifications of the 4U Ceph OSD Nodes:

2.2.10.3.   DC Output

2.2.12.3.1.   1000W: +12V/83A; +5Vsb/4A

2.2.12.3.2.   1280W: +12V/106.7A, +5Vsb/4A

These items are deleted.
3.6.3. 19.8W 3.6.3. 19.8W max
4.12.1.1. 550W AC power supplies 4.12.1.1. 550W maximum AC power supplies
“lowline full load” and “Output Power” specifications under the “10/40Gbps Layer 3 Ethernet Switches” :

4.12.1.2.2.2.   7.5A input @ 90V (lowline full load)

4.12.1.2.5.   Output Power

4.12.1.2.5.1.   12V output, 45A max, 540W

4.12.1.2.5.2.   3.3V output, 3A max, 9.9W

4.12.1.2.5.3.   550W DC output maximum continuous

These items are deleted.
Supply, Delivery, Installation and Configuration of One (1) Lot of Data Warehouse System
1.1.2. 920W Redundant 1.1.2. 920W maximum redundant
1.1.9.1 Two (2) 920W 1U Redundant PSU with quiet mode 1.1.9.1 Two (2) 920W maximum 1U Redundant PSU with quiet mode
1.2.7.5.1. Four (4) Rear USB 2.0 ports 1.2.7.5.1. Four (4) USB 2.0 ports
1.2.7.4.2. Four (4) USB 2.0 ports This item is deleted.
1.2.7.7. One (1) Fast UART 16550 port /1 Header 1.2.7.7. One (1) Fast UART port
“DC Output” specifications of the “Storage Nodes” :

1.2.12.3.   DC Output

1.2.12.3.1.   4A @ +5V standby

1.2.12.3.2.   75A @ +12V

These items are deleted.
2.6.3. 19.8W 2.6.3.  19.8W max
3.12.1.1. 550W AC power supplies 3.12.1.1. 550W maximum AC power supplies
“lowline full load” and “Output Power” specifications under the “10/40Gbps Layer 3 Ethernet Switches” :

3.12.1.2.2.2.   7.5A input @ 90V (lowline full load)

3.12.1.2.5.   Output Power

3.12.1.2.5.1.   12V output, 45A max, 540W

3.12.1.2.5.2.   3.3V output, 3A max, 9.9W

3.12.1.2.5.3.   550W DC output maximum continuous

These items are deleted.
Supply, Delivery, Installation and Configuration of One (1) Lot of Management Cluster System
1.1.2. redundant 700W PSU 1.1.2. redundant700/750W maximum PSU
1.2.8.4. Two (2) rear USB 2.0 ports 1.2.8.4. Two (2) USB 2.0 ports
1.2.8.5.   Four (4) via header USB 2.0 ports This item is deleted.
1.2.8.8. One (1) Fast UART 16550 serial port 1.2.8.8. One (1) Fast UART port
1.2.12.1. 700W/750W redundant 1.2.12.1. 700/750W maximum redundant
1.2.12.2.1. 700W @ 100-140V, 50-60Hz, 8.5-6A 1.2.12.2.1. 700W @ 100-140V, 50-60Hz, 8.5-6A or equivalent rating if less than 700W
1.2.12.2.2. 750W @ 180-240V, 60-50Hz, 5-3.8A 750W @ 180-240V, 60-50Hz, 5-3.8A or equivalent rating if less than 750W
“DC Output”  and “Power Distributor” specifications of the “Monitor Server” :

1.2.12.3.   DC Output

1.2.12.3.1.   At +5V standby, 3A

1.2.12.3.2.   At +12V, 700W: 58A @ 100-140V

1.2.12.3.3.   At +12V, 750W: 62A @180-240V

1.2.12.4.   Power Distributor

1.2.12.4.1.   +5V, 25A

1.2.12.4.2.   +3.3V, 25A

1.2.12.4.3.   -12V: 0.6A

These items are deleted.
2.1.2. 1280 or 1620W Redundant 2.1.2. 1280 or 1620W maximum Redundant
2.1.7.3. Two (2) 1280W 1U redundant single output PSU 2.1.7.3. Two (2) 1280W maximum 1U redundant single output PSU
2.2.6.3.1. Two (2) Rear USB 2.0 ports 2.2.6.3.1. Two (2) USB 2.0 ports
2.2.6.5. One (1) Fast UART 16550 port /1 Header 2.2.6.5. One (1) Fast UART port
2.2.10.1. 1280 or 1620W redundant 2.2.10.1. 1280 or 1620W maximum redundant
2.2.10.2.1. 1000W @ 100-140V, 50-60Hz, 8-12A 2.2.10.2.1. 1000W @ 100-140V, 50-60Hz, 8-12A or equivalent rating if less than 1000W
2.2.10.2.2. 1280W @ 180-240V, 50-60Hz, 6-8A 2.2.10.2.2. 1280W @ 180-240V, 50-60Hz, 6-8A or equivalent rating if less than 1280W
DC Output” specifications of the “Compute Servers” :

2.2.10.3.   DC Output

2.2.10.3.1.   1000W: +12V/83A; +5Vsb/4A

2.2.10.3.2.   1280W: +12V/106.7A, +5Vsb/4A

These items are deleted.
3.4.8. 600W 3.4.8. 600W max
4.6.3. 19.8W 4.6.3. 19.8W max
5.12.1.1. 550W AC power supplies 5.12.1.1. 550W maximum AC power supplies
“lowline full load” and “Output Power” specifications under the “10/40Gbps Layer 3 Ethernet Switches” :

5.12.1.2.2.2.   7.5A input @ 90V (lowline full load)”

5.12.1.2.5.   Output Power

5.12.1.2.5.1.   12V output, 45A max, 540W

5.12.1.2.5.2.   3.3V output, 3A max, 9.9W

5.12.1.2.5.3.   550W DC output maximum continuous

These items deleted.
Supply, Delivery, Installation and Configuration of One (1) Lot of Server Management Software
1.2.1. Quantity of licenses must be sufficient for the  Management Cluster System mentioned in the One (1) Lot of Government Common Platform Hardware’s Terms of Reference 1.2.1. Quantity of licenses must be sufficient for the One (1) Lot of Government Common Platform Hardware’s Terms of Reference

 

Original Provision Amended Provision
Section VII. Technical Specifications
LOT 2: Supply, Delivery, Installation and Configuration of the One (1) Lot of Government Common Platform Software
Service Specifications:

7. Configuration of Server Management Software capability

This item is deleted

 

5. Server Management Software This item is deleted and moved to Lot 1 Supply, Delivery, Installation and Configuration of the One (1) Lot of Government Common Platform Hardware
Scope of Work

1. The contractor shall deliver, install, configure and make operational the server, storage, and network infrastructure within four (4) months upon availability of hardware but not to exceed eight (8) months from Notice to Proceed (NTP).

1.        SScope of Work:

2.         11. The contractor shall deliver, install, configure, and mae operational the server, storage and network infrastructure within sixty (60) days upon availability of hardware.

All terms, conditions and instructions to bidders specified in the Bidding Documents inconsistent with this Bid Bulletin are hereby superseded and modified accordingly.

Kindly use the following forms attached in this Supplemental Bid Bulletin:

  • Revised Technical Specification as of 11November 2015
  • Revised Technical Specification as of 11 November 2015

 

To download this bid bulletin, click on the link below:

Supplemental Bid Bulletin No. 3 – Supply, Delivery, Installation, Configuration of Government Common Platform Hardware and Software System

 

For information and guidance of all concerned.

Issued this 11thday of November 2015.

 